Matter Thermostat setpoint limits and deadband are shared across thermostat endpoints #3264
Description
Summary
The driver supports multi-thermostat devices (notably the heat-pump profile), but caches thermostat setpoint limits and MinSetpointDeadBand with device-wide set_field() keys. Reports from one thermostat endpoint can therefore overwrite the constraints used for another endpoint.
Validated against main commit 43f47501b217336d17ed2fc92b64d08971f305ce.
Affected code
attribute_handlers.lua lines 151-185 stores deadband and heat limits without the reporting endpoint:
function AttributeHandlers.min_setpoint_deadband_handler(driver, device, ib, response)
local val = ib.data.value / 10.0
device:set_field(fields.setpoint_limit_device_field.MIN_DEADBAND, val, { persist = true })
device:set_field(fields.setpoint_limit_device_field.MIN_SETPOINT_DEADBAND_CHECKED, true, {persist = true})
end
...
device:set_field(minOrMax, val)
local min = device:get_field(fields.setpoint_limit_device_field.MIN_HEAT)
local max = device:get_field(fields.setpoint_limit_device_field.MAX_HEAT)capability_handlers.lua lines 171-245 correctly resolves the target thermostat endpoint, but validates against the same device-wide fields:
local endpoint_id = thermostat_utils.component_to_endpoint(device, cmd.component, clusters.Thermostat.ID)
...
local deadband = device:get_field(fields.setpoint_limit_device_field.MIN_DEADBAND) or 2.5
...
local min = device:get_field(fields.setpoint_limit_device_field.MIN_HEAT) or MIN_TEMP_IN_C
local max = device:get_field(fields.setpoint_limit_device_field.MAX_HEAT) or MAX_TEMP_IN_CThe driver already contains endpoint-field helpers in thermostat_utils/utils.lua lines 22-28:
function ThermostatUtils.get_field_for_endpoint(device, field, endpoint)
return device:get_field(string.format("%s_%d", field, endpoint))
end
function ThermostatUtils.set_field_for_endpoint(device, field, endpoint, value, additional_params)
device:set_field(string.format("%s_%d", field, endpoint), value, additional_params)
endFailure mechanism
Matter thermostat attributes are endpoint-scoped. The driver's cached constraints are not. On a device with two Thermostat server endpoints, the last limit/deadband report wins globally even though commands are routed to the correct endpoint.
Reproduction case
Use a composed/heat-pump device with two thermostat endpoints:
EP 2: AbsMinHeatSetpointLimit = 5 C, AbsMaxHeatSetpointLimit = 30 C
EP 3: AbsMinHeatSetpointLimit = 15 C, AbsMaxHeatSetpointLimit = 25 C
- Report the EP 2 limits.
- Report the EP 3 limits afterwards.
- Send
setHeatingSetpoint(10)to the SmartThings component mapped to EP 2. - The command handler resolves EP 2 correctly, but reads the device-wide cached range last written by EP 3 (15-25 C).
- The valid EP 2 command is rejected locally.
MinSetpointDeadBand can be overwritten in the same way.
Expected behavior
Each thermostat component/endpoint must be validated against the limits and deadband reported by that same Matter endpoint.
Proposed fix
Store and retrieve thermostat constraints with the reporting/target endpoint rather than device-wide keys. The driver already provides get_field_for_endpoint() and set_field_for_endpoint() helpers, so this can be done without introducing a new storage abstraction.
For example:
function AttributeHandlers.min_setpoint_deadband_handler(driver, device, ib, response)
if ib.data.value == nil then
return
end
local val = ib.data.value / 10.0
thermostat_utils.set_field_for_endpoint(
device,
fields.setpoint_limit_device_field.MIN_DEADBAND,
ib.endpoint_id,
val,
{ persist = true }
)
device:set_field(
fields.setpoint_limit_device_field.MIN_SETPOINT_DEADBAND_CHECKED,
true,
{ persist = true }
)
endThe setpoint-limit handlers should likewise cache and combine limits on the reporting endpoint:
thermostat_utils.set_field_for_endpoint(device, minOrMax, ib.endpoint_id, val, { persist = true })
local min = thermostat_utils.get_field_for_endpoint(
device, fields.setpoint_limit_device_field.MIN_HEAT, ib.endpoint_id
)
local max = thermostat_utils.get_field_for_endpoint(
device, fields.setpoint_limit_device_field.MAX_HEAT, ib.endpoint_id
)And command validation should use the endpoint already resolved from the SmartThings component:
local endpoint_id = thermostat_utils.component_to_endpoint(
device, cmd.component, clusters.Thermostat.ID
)
local deadband = thermostat_utils.get_field_for_endpoint(
device, fields.setpoint_limit_device_field.MIN_DEADBAND, endpoint_id
) or 2.5
local min = thermostat_utils.get_field_for_endpoint(
device, fields.setpoint_limit_device_field.MIN_HEAT, endpoint_id
) or MIN_TEMP_IN_C
local max = thermostat_utils.get_field_for_endpoint(
device, fields.setpoint_limit_device_field.MAX_HEAT, endpoint_id
) or MAX_TEMP_IN_CApply the same endpoint scoping to cooling constraints and to range events emitted by temperature_handler_factory().
If the configurable-limit issue is fixed at the same time, both the absolute (ABS_*) and configurable (MIN_* / MAX_*) fields should be endpoint-scoped, with configurable values taking precedence over absolute values.
Suggested regression test
Extend test_matter_heat_pump.lua so thermostatOne and thermostatTwo report different ranges/deadbands, then issue setpoint commands to both components and verify each command is validated only against its mapped endpoint's values.